Switchboards
and renovating panels with VTA971 control system are suitable
for the lift reconstruction and the modernization of obsolete
technology such as traction drive and hydraulic lift. They are
also suitable for all new lift technology. The product meets the
requirements of ÈSN EN 81-1 and ÈSN EN 81-2 standards.
The
renovating panels contain a control unit, protecting parts
and output power parts, which all fit into the original
switchboard boxes. The switchboards include additional control
and light transformers.
Our
company supplies new covers with IP42 cover. The switchboard
covers have enough space for modules with a remote diagnostic
system. There is space for placement of additional modules which
extend the basic system functions.
Particular
switchboards and renovating panels are supplied with a various
number of landing stages; the standard is 8 and maximum 32. It
is possible to supply the equipment in accordance with to the
customer’s requirements for the type of emergency power supply,
lift car lighting, type of the location indicator for cage at
landings, stage up/down button back lighting and the like. The
order can be supplied in installments.
It
is possible to supply the switchboards without the
control transformers or control system VTA971.
Advantages:
- All switchboards and renovating panels
- prior to delivery to the customer – undergo a test
in simulating devices which ensure the error-free run after
correct installation by customer.
- The switchboards include checkout, field-tested and
bargain package power parts.
- The switchboard terminal block is installed to
enable easy and fast connection to the original technology.
- It is possible to supply the product with shaft
cabling, belt cables and connectors with modular design –
(for easy and fast installation),
fast interchangeability of component parts
- The shape and the size of the switchboard box makes
it possible to exchange of the original switchboard with
minimum mechanical modification.
- The size of the mounting panels for given
technologies are suitable for the size of the original cover.
- The option of the cover with FAB lock or type RU3 or
RU5 lock.
Technical parameters:
|
Cover |
IP42 |
|
Power supply |
3x400 V+PEN
|
|
Power supply of magnets |
48 V DC, 48/12 DC |
|
Brake |
48 V DC, 230 V AC |
|
Door |
manual control, full automatic |
|
Cage lighting |
24/230 V AC – bulb
230 V AC – fluor tube |
|
Light signaling |
direction light 10 V AC
flashing 10 V
LED 24 V |
|
Audio signaling |
10 V AC – gong, landing run, overloading |
|
Location indicator of cage |
seven-segmented
matrix-roto
light series
audio |
|
Controlling |
programmable, collecting, SIMPLEX |
|
Extension device |
remote diagnostic with GSM
tensiometer sensing of the liftcar load |
|
Door catch |
FAB; RU3 or RU5 |
|